Home & Construction

Preliminary HVAC Heating & Cooling Load Estimator

Updated Aug 25, 2026 Reviewed Aug 25, 2026
Estimate block-level transmission, infiltration, solar, internal sensible and latent heating/cooling loads from explicit envelope, weather, humidity and occupancy inputs in SI or imperial units.

Auditable preliminary block load

Enter envelope, design weather, air exchange and internal gains

Enter net component areas. Do not include window and door areas again inside opaque wall area.

Enter W/m² in SI mode or Btu/(h·ft²) in imperial mode.

Combined design infiltration and outdoor-air exchange for this simplified model.

Use zero unless justified by duct location and leakage information.

This is visible scenario input, not an equipment-selection recommendation.

Not Manual J and not equipment selection
Use an ACCA-approved load procedure and qualified designer for equipment sizing, room-by-room loads, ducts and compliance documentation.

Result

Calculation summary

Enter values to see the result

Your result, breakdown, assumptions, and warnings will appear here.

Heating and cooling balance

Sensible and latent block load

Live preview
Preliminary heating load7.6 kWTotal cooling load9.12 kW · SHR 79.5%SensibleLatentPreliminary comparison — not Manual J
Preliminary heating load 7.6 kW, cooling load 9.12 kW and sensible heat ratio 79.5%.

How to use this calculator

  1. 1Choose SI or imperial thermal-property inputs and enter conditioned floor area, ceiling height and explicit envelope component areas.
  2. 2Enter project-specific U-values, window SHGC, shading and design solar irradiance instead of selecting a generic building age preset.
  3. 3Enter local indoor and outdoor heating/cooling design temperatures, relative humidity, air changes, occupants and internal gains.
  4. 4Use duct and sizing allowances only when justified, then treat the result as a preliminary block-load comparison rather than equipment selection.

Formula

Transmission = Σ(U × area × ΔT); infiltration sensible = mass airflow × cp × ΔT; latent = mass airflow × hfg × humidity-ratio difference

Cooling also includes entered solar and internal sensible/latent gains. User-entered duct and sizing allowances are applied multiplicatively.

Calculation steps

  • Convert all areas, heights, temperatures, U-values and solar inputs to SI units.
  • Sum U × area for walls, ceiling, floor, windows and doors, then apply heating and cooling temperature differences.
  • Convert air changes per hour and building volume to airflow and calculate sensible infiltration.
  • Estimate cooling latent infiltration from indoor and outdoor humidity ratios at standard atmospheric pressure.
  • Add window solar gain, occupants, lighting and appliance loads.
  • Apply explicit allowances and report heating, sensible cooling, latent cooling, total cooling, SHR, kW, Btu/h and cooling tons.

Worked example

The default 150 m² example uses explicit envelope U-values, 0.5 ACH, four occupants and entered design conditions. The result separates transmission, outside-air, solar and internal loads so the assumptions can be audited instead of hiding one BTU-per-area rule.

Assumptions

  • This is not ACCA-approved software and does not perform ANSI/ACCA Manual J. It is an educational preliminary block-load estimate only.
  • Envelope areas are entered as net component areas and are not inferred from floor area. U-values and SHGC must match the actual assemblies.
  • All surfaces use one outdoor design temperature; ground coupling, adjacent zones, thermal mass, exposure diversity and hourly solar geometry are simplified.
  • Air changes represent combined infiltration and entered outdoor-air exchange. Wind, stack effect, mechanical ventilation schedules and heat recovery are not modeled separately.
  • Humidity ratio uses entered dry-bulb temperature and relative humidity at standard atmospheric pressure.
  • Duct location/leakage, room-by-room distribution, blower heat, moisture migration, dehumidification targets, equipment performance, safety factors and code documentation require professional procedures.

Sources

Frequently asked questions

Is this a Manual J calculator?

No. It is not ACCA-approved and cannot produce a compliant Manual J report.

Can I select equipment from the displayed tons?

No. Equipment selection requires an approved load procedure, manufacturer performance data and the applicable equipment-selection standard.

Why enter component areas and U-values?

Actual envelope geometry and thermal properties are more transparent than a single BTU-per-square-foot shortcut.

What is sensible heat ratio?

It is sensible cooling divided by total sensible plus latent cooling under the entered design assumptions.

Are internal gains credited against heating?

No. This simplified estimator does not reduce the heating load for occupants, lights or appliances.

Why can humidity change cooling load?

Humid outdoor air adds latent moisture-removal load when its humidity ratio exceeds the indoor design condition.

Insulation Calculator
Estimate insulation packages for attics, walls, floors, or combined regions using measured area, openings, waste, and product coverage.
Area Calculator
Calculate the area of a rectangle from its length and width, then convert the result between metric and imperial area units.
Electricity Cost Calculator
Estimate device energy use and cost by power, quantity, daily hours, days, and a user-entered price per kilowatt-hour.
Unit Converter
Convert length, area, volume, mass, temperature, and speed with explicit units and adjustable display precision.